- Archestra License Manager Missing
- Install Archestra License Manager Job
- Install Archestra License Manager Duties
Step 17: Launch “ArchestrA License Manager” by going to Start-All Programs-Invensys-License Manager-ArchestrA License Manager Step 18: Check the box “Do not ask this question again”. Then click the button “No”. The ArchestrA License Manager is included on the Wonderware CDs. It is a common component installed by all products requ iring a license. When you configure the computer for remote license. ArchestrA License Manager User’s Guide Chapter 1 Using the ArchestrA License Manager This guide describes the ArchestrA License Manager and how to use it to install, maintain, and delete licenses and license servers on local and remo te computers. The guide also describes how to use the ArchestrA License Manager with hardware keys. This video walks through an example of offline (no internet needed) activating a Wonderware license using the Schneider Electric License Manager. License as mentioned above, will also be provided via email. No licenses will be shipped on CD. Schneider Electric Licensing System The Licensing System is composed of a browser-based License Manager and a License Server that together allow you to share and deliver licenses for your installed products. The License Manager is browser-based and very.
This TechNote gives you important instructions to be performed on each platform at which you want to deploy the DIObjects to avoid having licensing issue in runtime when running new versions from DIObject , which use the new Archestra License not suitelink.lic for example DIMBTCP 3.0 sp1 and DIABCIP 5.0, inside Wonderware Application Server 3.1 SP3 Patch 1 .
Application Versions
- Application Server 3.1 SP3 P01
- DI MBTCP 3.0 SP1
- DI ABCIP 5.0
OPERATING SYSTEM
Windows Server 2008 R2
SITUATION
Archestra License Manager Missing
When running newer DASSERVER it stops periodically , getting Information message in your logger says that <DASERVER name > Please install a valid license for this DAServer product as shown in fig.1 below. trying with external demo license and getting same issue.
Figure 1: License invalid info message
SYMPTOMS
DAServer now uses the ArchestrA License Manager and the common ArchestrA license file.
Install Archestra License Manager Job
If you are still using software versions that use the wwsuite.lic license file, and you do not have an ArchestrA.lic license file with the correct feature line you need to add it, you need to run InitLicense.wsf file included with the CD image to initialize the new ArchestrA Licensing sub-system.
ACTION
If you are running Wonderware Application Server 3.1 SP3 Patch 1 or older, you must perform the following functions on each platform where you want to deploy the MBTCP DIObjects to it, Please follow below steps.
- Undeploy DIObjects. and close IDE.
- Install two Microsoft components manually.NET 4.0 Framework and Visual C++ 10.0 SP1 run-time redistributable components.
- Run the InitLicense.wsf file included with the CD image, fig.2, to initialize the new ArchestrA Licensing sub-system.
Figure 2: InitLicense.wsf file in DIObject CDWe will see license subsystem Initialization success message as shown in Figure 3 (below).
Figure 3: License subsystem initialization success message - Launch ArchestrA IDE and deploy DIObjects again.
Script in InitLicense.wsf
<job>
<script language=”VBScript”>
Set oShell = CreateObject(“WScript.Shell”)
If CInt(oShell.RegRead(“HKLMSOFTWAREMicrosoftWindows NTCurrentVersionCurrentBuildNumber”)) > 3790 Then
If WScript.Arguments.Named.Exists(“elevated”) = False Then
‘Launch the script again as administrator
CreateObject(“Shell.Application”).ShellExecute “wscript.exe”, “””” & WScript.ScriptFullName & “”” /elevated”, “”, “runas”, 1
WScript.Quit
Else
‘Change the working directory from the system32 folder back to the script抯 folder.
Set oShell = CreateObject(“WScript.Shell”)
oShell.CurrentDirectory = CreateObject(“Scripting.FileSystemObject”).GetParentFolderName(WScript.ScriptFullName)
End If
End If
Dim WSHShell, RegKey, OsType, FolderPath, ProgramFilesPath
Set WshShell = CreateObject(“WScript.Shell”)
OsType = WshShell.RegRead(“HKLMSYSTEMCurrentControlSetControlSession ManagerEnvironmentPROCESSOR_ARCHITECTURE”)
FolderPath = “Common FilesArchestrALicense”
Install Archestra License Manager Duties
If OsType = “x86” Then
RegKey = “HKLMSOFTWAREWonderwareLicense”
ProgramFilesPath = wshShell.ExpandEnvironmentStrings(“%PROGRAMFILES%”)
FolderPath = ProgramFilesPath + FolderPath
‘wscript.echo “Windows 32bit system detected”
Else
If OsType = “AMD64” Then
RegKey = “HKLMSOFTWAREWow6432NodeWonderwareLicense”
ProgramFilesPath = wshShell.ExpandEnvironmentStrings(“%PROGRAMFILES(x86)%”)
FolderPath = ProgramFilesPath + FolderPath
‘wscript.echo “Windows 64bit system detected”
End If
End If
WSHShell.RegWrite RegKey & “FlexLicFileDir”, FolderPath, “REG_SZ”
wscript.echo “ArchestrA Licensing sub-system initialization succeeded.”
</script>